Neutral Current

Excessive Neutral Current in Three Phase, Wye-Connected Systems

Introduction

While there are a few papers available on the Internet discussing the issue of excessive neutral current in wye-connected three-phase systems, few give a complete understanding of the problem. Furthermore, the vase majority of electricians and the standards fail to grasp the issue. With incandescent light bulbs, linear loads, vanishing and more other lighting technologies and electronic (non-linear) loads becoming dominate, the issue is becoming more relevant. The result is dangerously excessive current on the phase systems and “home runs” with a common the neutral wire.
Therefore, I decided to perform numerous computer simulations and write this paper, given the following experiences.
When would the neutral current on a three phase system be zero? The accepted understanding is correct if and only if the following conditions are all met:

Ammeters

Most inexpensive digital and hand-held ammeters will not yield a correct Root-Mean-Square (RMS) current reading under the conditions discussed in this paper. These meters generally read an average value and compute an RMS value under the assumptions that the current is both sinusoidal and 60 Hz. However, the currents are seldom sinusoidal and are highly distorted, resulting in an incorrect reading. The currents, mainly the neutral current, may be mostly third harmonic, 180 Hz, with little or no 60 Hz component. A significant amount of higher harmonics may also be present. Only an analog ammeter with a non-linear scale is designed to correctly read RMS currents accurately. Other ammeters may be in error by as much as 50%.

Effects of Non-Linear Loads

For reference, the following graphic shows the sinusoidal voltage waveforms on each of the three phases of a three phase, wye-connected system. The magnitude shown is scaled to the range of -1 to +1, whereas the 120/208 RMS Volt system would have voltages ranging from -170 to +170 volts, phase to neutral. The instantaneous sum of all three voltages at any one time will be zero. Unfortunately, most electricians believe that the currents are also sinusoidal, which is seldom the case and the subject of this paper. Non-linear loads result in non-sinusoidal or distorted current waveforms.
A large number of computer simulations have shown that takes surprisingly little non-linearity to obtain a significant neutral current, equal to or greater than the per-phase current. Not much more nonlinearity is needed to obtain the theoretical maximum neutral current of √3=1.732 times the perphase current. Therefore, the 20 Amp lighting circuit I worked on could easily have 34.6 Amps on its 12 AWG neutral conductor. This is clearly excessive.

The graphic below shows the neutral current for a relatively small degree of non-linearity in the loads. The voltage on one phase is shown as a horizontal reference. Note that the current is entirely third harmonic current, 180 Hz, with no 60 Hz component. Again the magnitude is scaled to the range of -1 to +1. Even with this small degree of non-linearity, the neutral current was approximately equal to the per-phase current.

The next graphic, below, should provide a greater understanding of the mechanism for a greater degree of non-linearity. In a linear system, two or more of the loads carry current at any one time, resulting in a cancellation of current on the neutral wire. In the non-linear load case, shown below, only one phase conducts current at any one time, and the currents therefore add, rather than subtract, on the neutral wire. Therefore, the graphic shows which phase is introducing current to the neutral wire for each pulse. Because the currents add on an RMS basis, the neutral current will be √3=1.732 times the current on any phase, rather than three times the phase current. Again, the neutral current has no 60 Hz component and is largely third harmonic current at 180 Hz, with components at 360, 540, 720, … Hz. The letters, A, B or C, indicate which phase is supplying current to the neutral wire at any one time. Again, the A-phase voltage is shown as a horizontal reference in blue.

Note: There are Internet videos showing 1st and 3rd harmonic currents like those on the right, with the combined current shown at the lower right. However, these scenarios apply to specific loads, such as variable speed drives (motors). These loads are not the subject of this paper. The waveform above simulates and is more typical of modern lighting and electronic loads.

Effects of Differing Power Factors

A number of computer simulations were performed on a three phase system with balanced loads, but differing power factors on each phase. Again, it was possible to obtain significant neutral currents, up to 1.73 times the current on any one phase. The graphic below shows, in red, a case where a neutral current of 1.4 times the phase current was obtained with power factors of 0.63 leading (capacitive load) and 0.63 lagging (inductive) loads on two of the phases. The third phase had a power factor of 1.0 (resistive load).

RV or Apartment on 2 Phases.

Many large recreational vehicles (RVs) with 4-prong plugs use two 120 Volt legs with a common neutral conductor. Many campgrounds will supply two phases of a three phase 120/208 wye-connected system to each site. All loads are generally 120 Volt loads, with no loads running on 208 or 240 Volts. A similar situation may exist for apartment units in a large apartment building, although they will have 208 Volt loads.
Computer simulation shows that the neutral current for linear loads in the RV case will equal the phase current, but phase shifted. Fortunately, RVs do not have a significant amount on non-linear loads, other than the microwave oven. If an RV did have largely non-linear loads, the neutral current could theoretically approach √2=1.414 times the phase current and the neutral current waveform could be quite bizarre, as shown in the graphic below. Thus, a 50 Amp RV service could see 70.7 Amps on the neutral wire, although this is unlikely and the normal 6 AWG wire is sufficient.

NFPA 70: 2020 National Electrical Code

The National Electrical Code really drops the ball on this topic, which I first saw in the mid-1970s. As a result, many electricians still believe and teach facts that have not been true since the says of incandescent light bulbs.
Article 310.15 (E), page 70-160:
Neutral Conductor. Neutral conductors shall be considered current carrying in accordance with any of the following:

Third Harmonic Current Elimination

Given the fact that most lighting and electronic loads are non-linear, a large amount of harmonic current exists in modern wye-connected, three-phase power systems. Harmonic current is eliminated by the following three methods:

Conclusions and Recommendations

For example, let us suppose that I was installing a 3-phase sub-panel and then running single phase circuits out of that panel. I would run a single +4 AWG oversize neutral from the main panel to the subpanel. Then I would run separate neutrals for each single phase circuit out of the sub-panel.

Acknowledgments

All computer simulations mentioned in this paper were written by the author in the Python programming language.
The graphics shown in this paper were generated using graphic calculator.
Two papers on the topic were also held by the Institute of Electrical and Electronics Engineers (IEEE), but are accessible only by IEEE members. Although the author had read those papers, he is unable to provide citations for them.